CVE-2016-7114

Improper Authentication

Published: Sep 06, 2016 | Modified: Mar 23, 2018
CVSS 3.x
8.8
HIGH
Source:
NVD
CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
CVSS 2.x
9 HIGH
AV:N/AC:L/Au:S/C:C/I:C/A:C
RedHat/V2
RedHat/V3
Ubuntu

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.87; SIPROTEC 7UT686 : All versions < V 4.02; SIPROTEC 7SD686 : All versions < V 4.05; SIPROTEC 7SJ66 : All versions < V 4.30. Attackers with network access to the devices web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. A legitimate user must be logged into the web interface for the attack to be successful.

Weakness

When an actor claims to have a given identity, the product does not prove or insufficiently proves that the claim is correct.

Affected Software

Name Vendor Start Version End Version
En100_ethernet_module_firmware Siemens 4.28 (including) 4.28 (including)

Potential Mitigations