CVE Vulnerabilities

CVE-2018-5459

Improper Authentication

Published: Feb 13, 2018 | Modified: Oct 09, 2019
CVSS 3.x
9.8
CRITICAL
Source:
NVD
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS 2.x
7.5 HIGH
AV:N/AC:L/Au:N/C:P/I:P/A:P
RedHat/V2
RedHat/V3
Ubuntu

An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.

Weakness

When an actor claims to have a given identity, the product does not prove or insufficiently proves that the claim is correct.

Affected Software

Name Vendor Start Version End Version
Pfc200_firmware Wago * 02.07.07(10) (excluding)

Potential Mitigations

References