CVE Vulnerabilities

CVE-2020-27738

Access of Memory Location After End of Buffer

Published: Apr 22, 2021 | Modified: Nov 21, 2024
CVSS 3.x
7.4
HIGH
Source:
NVD
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H
CVSS 2.x
5.8 MEDIUM
AV:N/AC:M/Au:N/C:P/I:N/A:P
RedHat/V2
RedHat/V3
Ubuntu

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a read access past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition.

Weakness

The product reads or writes to a buffer using an index or pointer that references a memory location after the end of the buffer.

Affected Software

Name Vendor Start Version End Version
Simotics_connect_400_firmware Siemens * 0.5.0.0 (excluding)

References