A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
An exact value or random number can be precisely predicted by observing previous values.
Name | Vendor | Start Version | End Version |
---|---|---|---|
Capital_vstar | Siemens | * | * |
Nucleus_net | Siemens | * | 5.2 (excluding) |
Nucleus_source_code | Siemens | * | * |
Pluscontrol_1st_gen | Siemens | * | * |