A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.
The product does not sufficiently track and release allocated memory after it has been used, which slowly consumes remaining memory.
Name | Vendor | Start Version | End Version |
---|---|---|---|
Simatic_drive_controller_cpu_1504d_tf_firmware | Siemens | * | 2.9.4 (excluding) |