CVE Vulnerabilities

CVE-2021-41545

Published: May 10, 2022 | Modified: May 19, 2022
CVSS 3.x
7.5
HIGH
Source:
NVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CVSS 2.x
5 MEDIUM
AV:N/AC:L/Au:N/C:N/I:N/A:P
RedHat/V2
RedHat/V3
Ubuntu

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.

Affected Software

Name Vendor Start Version End Version
Desigo_dxr2_firmware Siemens * 01.21.142.5-22 (excluding)

References