CVE Vulnerabilities

CVE-2022-31204

Cleartext Transmission of Sensitive Information

Published: Jul 26, 2022 | Modified: Nov 21, 2024
CVSS 3.x
7.5
HIGH
Source:
NVD
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
CVSS 2.x
RedHat/V2
RedHat/V3
Ubuntu
root.io logo minimus.io logo echo.ai logo

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.

Weakness

The product transmits sensitive or security-critical data in cleartext in a communication channel that can be sniffed by unauthorized actors.

Affected Software

NameVendorStart VersionEnd Version
Sysmac_cs1_firmwareOmron*4.1 (excluding)

Potential Mitigations

References